VT335t IT Monitoring unit

Description

The VT335 / IT Room Monitoring Unit can be used for remote environmental monitoring in small IT rooms. Its primary features include:

  • Environmental Monitoring: Measures temperature, humidity, voltage, access, smoke, dust, vibration, access, leakage, movement, airflow.

  • I/O Controller: 4 analog inputs, CAN input, 4 dry contacts IN, 2 relays 12V, SD, USB, extensions.

  • Scalability: Supports up to 800 elements, including sensors, virtual sensors, logic, notifications.

  • Built-in Web Interface: Provides a user-friendly interface, 100Mbit/s.

  • Extensions: LTE modem, Modbus, Reader.

  • Notifications: Telegram, push, mail; VPN, SMS and voice call in case of LTE modem built-IN.
  • Processor: 720Mhz dual-core Cortex-A7.

Use cases

  • Agricultural Settings: Manage humidity and temperature in greenhouses to optimize crop growth.
  • Rack / Cabinet manufacturers: Server rack or Electrical cabinet environmental monitoring of parameters adds an additional value when selling racks and adds technological innovation and value to the company.
  • Data Centers: Monitor critical environmental conditions to safeguard sensitive equipment.
  • Industrial Applications: Control operational equipment and automate responses to environmental changes.

Hardware specifications

- Analog sensor range

- VT408 analog sensor extension unit adds more ports

- Plug & Play

- 5 level thresholds

- Hysteresis for alert delay if the sensor value jumps to fast

- Linear formula for sensor value adjustments

- Math element for calculating your own formulas

- Graphs, multi-graphs

- Ethernet 10/100 Base-T port, provides an Ethernet connection

- VT740 LTE modem ordered separately

- SMS notifications

- Ethernet, network reservation

- Connect USB100 camera for JPEG stream notifications

- Use USB hub

- Use USB Flash for logs

- Upgrade firmware over USB

- Connect digital CAN sensors in a daisy chain

- CAN sensor range

- Connect CAN extensions

- VT440 dry contacts extension

- VT408 analog sensor extension

- Restart button

- Factory reset

- N-R switch

- Activity, Error, Alarm, CAN

- x2 12V relays

- Receive voltage free signals from devices and sensors

- E.g. door sensor, window sensor, UPS, diesel generators, circuit breakers, alarm system, control panels, and other industrial equipment.

- Connect KMS-30 access sensor

- 12V DC

- 12V DC terminal, 2P, pitch 3.81mm

- Control VT103 alarm beacon

- Control VT105 strobe light

- Control VT11 relay contact switch

- Control other 12V DC devices

- Save logs to an SD card

- SD card is not included

- Up to 500Gb

- Temperature

- Voltage sensors for power supply inputs

- Chassis grounding

Extensions

VT7670 LTE slot modem

Allows to receive and send SMS notifications (2G, 3G). Provides Ethernet reservation over LTE (4G).

Extension slot

VT485r Reader extension

Allows to connect readers, and keypads with OSDP protocol support.

or

VT485m Modbus extension

Allows to monitor up to 32 Modbus RTU devices/meters/sensors.

Accessories

Advanced protocols

Vutlan supports most popular communication protocols & adding more...

SNMP v1, v2c, v3

Simple Network Protocol for connecting multiple Vutlan units to a single DCIM, NMS, and Infrastructure monitoring software.

+

Modbus RTU,
Modbus TCP

Modbus serial communication protocol designed for industrial automation systems, and industrial meters.

+

OSDPv2 RS485

Open Supervised Device Protocol is an access control communications standard for readers, & keypads.

+

and other...

DHCP, HTTP, HTTPS, SMTP, FTP, Syslog, TLS, DynDNS, RADIUS, SSL, NTP, OpenVPN

Pushing limits

The most powerful monitoring and control systems in the world!

OS Linux

v.6.2

Processors

720 MHz, 2 Cores

Maximum sensors

100 physical sensors

Maximum elements

700 virtual elements

Built-in web interface

All Vutlan monitoring devices have a built-in multilingual web interface for monitoring and managing the device.

Here you can configure notifications and alerts, logic schemes, user access rights, sensors and elements.

You can also view sensor graphs, logs and camera images.

Add more analog sensors using VT408 extension unit.

Each VT408 extension unit connected to the Vutlan monitoring device via the CAN bus adds the ability to connect 8 analog sensors to the system.

Sensors connected to the unit are automatically displayed in the system.

Add more Dry contacts using VT440

The VT440 / Dry Contacts extension unit increases the number of Dry contacts that can be connected to any Vutlan monitoring device.

Each VT440 device adds 32 dry contacts. Each VT440 + VT32 expansion module adds 64 dry contacts. 

A tab for monitoring and configuring dry contacts is available in the Vutlan device interface.

Connecting CAN sensors

You can connect multiple CAN devices to a CAN bus chain.

Each VT408 unit in the CAN bus chain adds 8 analog sensors. Each VT440 unit adds 32 or 64 dry contact inputs to the system.

An additional CAN12V-1A power supply is only required if the number of CAN devices in the CAN bus chain exceeds 12 pieces.

Centralized Infrastructure Management Software using SNMP protocol

No matter how complex your IT infrastructure is, you can manage all assets using DCIM SNMP software, infrastructure management software.

Vutlan supports SNMP v1, SNMP v2c, SNMP v3. Hence the data from Vutlan monitoring units can be monitored from any SNMP managemnt software package.