VT408D Sensor extension unit

€177.12
Tax included

Description

The VT408D Extension unit increases the number of analog sensors connected to any Vutlan monitoring device. 

All connected sensors are automatically detected and integrated into the system. CAN devices can be connected in a chain. 

DIN mounting.

Specifications

Device type:
CAN bus device
Network Interface:
CAN open
Inputs:
8 analog sensor ports, RJ11 6P4C CAN ports
Daisy chain:
Yes, can be connected in a chain with other CAN bus sensors and extensions.
Operating temperature:
-10° C to +80° C
Max. distance from the unit:
Max. bus length: 225m,
Max. length of analog sensor cables: 50-150m (depends on sensor type)
Maximum units in a chain:
You can install a maximum of 10 units, provided that no other CAN devices are installed in a CAN chain.
Power input:
12V DC
Dimensions:
Width 129, Height 28.6, Depth 56 mm
Mounting possibilities:
DIN rail 7mm depth, 15mm depth
Status Indicators:
Red (Error) / Green Led (Run)
TR switch:
Activate if the unit is the last unit in a CAN bus chain.
Origin of goods:
Made in EU
HS Code:
8471 50 000
GTIN:
8588009886464

Connecting CAN sensors

You can connect multiple CAN devices to a CAN bus chain.

Each VT408 unit in the CAN bus chain adds 8 analog sensors. Each VT440 unit adds 32 or 64 dry contact inputs to the system.

An additional CAN12V-1A power supply is only required if the number of CAN devices in the CAN bus chain exceeds 12 pieces.

Systems with CAN ports:

To read data from the CAN sensors, you need a Vutlan monitoring device with one or two CAN ports.